Environmental Conditions |
Operating temperature | -20°C to +60°C |
Storage temperature | -20°C to +85°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Mechanical |
Dimensions (HxWxD) | 109 x 23.5 x 104 mm |
Weight approx. | 160 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13...2.08 mm2AWG 26...14 stranded wire |
Screw terminal torque | 0.5 Nm |
Vibration | EC 60068-2-6 |
2...13.2 Hz | ±1 mm |
13.2...100 Hz | ±0.7 g |
Common |
Supply |
Supply voltage, universal | 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | ≤ 2.5 W |
Max. power dissipation | ≤ 2.0 W |
Isolation voltage |
Test voltage | 2.3 kVAC |
Input to any (working) | 250 VAC (reinforced) |
Relay to relay (working) | < 115 VAC (reinforced) |
Relay to analog (working) | > 115 VAC (basic) |
NPN to analog (working) | Isolated > 50 VDC |
Push-Pull / PNP to analog (working) | Shared ground with analog output |
Response time (0...90%, 100...10%)≤ 30 ms | |
Auxiliary supplies |
Sensor supply limitation (terminal 44) | 20 mA, 5...17 V |
Programming | PR 4500 communication interfaces |
Signal dynamics, output | 18 bit |
Signal / noise ratio | > 60 dB |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input | |
Frequency input | |
Frequency range | 0.001 Hz to 100 kHz |
Time range, time function | 10 μs to 999.9 s |
Max. frequency / min. pulse width, with input filter ON | 75 Hz / 8 ms |
Sensor specifications |
NAMUR, trig-level LOW / HIGH | ≤ 1.2 / ≥ 2.1 mA |
Tacho, trig-level LOW / HIGH | ≤ -50 mV / ≥ +50 mV |
NPN / PNP, trig-level LOW / HIGH | ≤ 4.0 V / ≥ 7.0 V |
TTL, trig-level LOW / HIGH | ≤ 0.8 V / ≥ 2.0 V |
S0, trig-level LOW / HIGH | ≤ 2.2 mA / ≥ 9.0 mA |
User-programmable trig-levels | -0.05...6.50 V 0.0...10.0 mA |
Output | |
Current output | |
Signal range | -23...+23 mA (bipolar) 0...23 mA (unipolar) |
Programmable standard ranges | 0...20, 4...20, S4-20, ±10 mA, ±20 mA |
Load ( at current output) | ≤ 600 Ω |
Load stability | ≤ 0.001% of span / 100 Ω |
Response time, programmable | 0.0...60.0 s |
Sensor error indication | 0 / 3.5 / 23 mA / none |
Current limit | ≤ 28 mA |
Buffered voltage output | |
Signal range | ± 11.5 V |
Programmable standard ranges | 0...5, 1...5, 0...10, 2...10, ± 5, ± 10 VDC |
Load, min. | > 2 kΩ |
Response time, programmable | 0.0...60.0 s |
Relay output | |
Relay functions | Setpoint, Window, Sensor error, Latch, Power and Off |
Hysteresis | 0...100% |
ON and OFF delay | 0...3600 s |
Sensor error reaction | Break / Make / Hold |
Max. voltage | 250 VAC / VDC |
Max. current | 2 A |
Max. AC power | 500 VA |
Frequency output | |
Frequency range | 0.001 Hz...100 kHz |
Prog. pulse time (f ≤ 500 Hz) | 1...1000 ms |
Pulse time > 500 Hz | Fixed 50% |
NPN / PNP / Push-Pull output | |
Isink max. | 130 mA |
Voltage drop 130 mA | < 1.5 VDC |
Ext. voltage (terminal 24) max. | 30 VDC |
Isource max. | 30 mA |
Vout | 24 VDC ± 10% |
Voltage | 5...24 VDC |