Environmental Conditions |
Operating temperature | -25°C to +70°C |
Storage temperature | -40°C to +85°C |
Calibration temperature | 20...28°C |
Relative humidity | < 95% RH (non-cond.) |
Protection degree | IP20 |
Installation in | Pollution degree 2 & meas. / overvoltage cat. II |
Mechanical |
Dimensions (HxWxD) | 113 x 6.1 x 115 mm |
Weight approx. | 70 g |
DIN rail type | DIN EN 60715/35 mm |
Wire size | 0.13...2.5 mm2/ AWG 26...12 stranded wire |
Screw terminal torque | 0.5 Nm |
Common |
Supply |
Supply voltage | 16.8...31.2 VDC |
Fuse | 400 mA SB / 250 VAC |
Max. required power | ≤ 1.2 W |
Max. power dissipation | 0.65 W |
Isolation voltage, test / working | 2.5 kVAC / 300 VAC (reinforced) |
Response time (0...90%, 100...10%) | ≤ 30 ms |
Auxiliary supplies |
Sensor supply limitation | 23 mA, 5...17 V |
Signal dynamics, output | 18 bit |
Long term stability, current, 1yr / 5yr at 25°C | ≤ 0.058% / ≤ 0.101% |
Long term stability, voltage, 1yr / 5yr at 25°C | ≤ 0.032% / ≤ 0.058% |
Accuracy | See manual for details |
EMC immunity influence | < ±0.5% of span |
Extended EMC immunity: NAMUR NE21, A criterion, burst | < ±1% of span |
Input |
Frequency input |
Frequency range | 0.001 Hz to 100 kHz |
Time range, time function | 10 μs to 999.9 s |
Max. frequency / min. pulse width, with input filter ON | 75 Hz / 8 ms |
Sensor specifications |
Tacho, trig-level LOW / HIGH | ≤ -50 mV / ≥ +50 mV |
NPN / PNP, trig-level LOW / HIGH | ≤ 4.0 V / ≥ 7.0 V |
TTL, trig-level LOW / HIGH | ≤ 0.8 V / ≥ 2.0 V |
S0, trig-level LOW / HIGH | ≤ 2.2 mA / ≥ 9.0 mA |
NAMUR, trig-level LOW / HIGH | ≤ 1.2 / ≥ 2.1 mA |
Special voltage / current input |
User-programmable trig-levels | -0.05...6.50 V 0.0...10.0 mA |
Output |
Current output |
Signal range, active | 0...23 mA |
Programmable signal ranges | 0 / 4...20 mA |
Load (current output) | ≤ 600 Ω |
Load stability | ≤ 0.001% of span / 100 Ω |
Response time, programmable | 0.0...60.0 s |
Sensor error indication | 0 / 3.5 / 23 mA / none |
Current limit | ≤ 28 mA |
Voltage output |
Signal range | ≤ 11.5 VDC |
Programmable signal ranges | 0...1; 0...5; 0...10; 0.2...1; 2...10 VDC |
Load (voltage output) | ≥ 10 kΩ |
Response time, programmable | 0.0...60.0 s |
Relay output |
Relay functions | Setpoint, Window and Latch |
Hysteresis | 0...100% |
ON and OFF delay | 0...3600 s |
Power On delay | 0...9999 s |
Sensor error reaction | Break / Make / Hold |
Max. voltage | 250 VAC / 200 VDC |
Max. current | 2 A |
Max. AC power | 500 VA |
Max. DC current, resistive load ≤ 30 VDC | 2 ADC |